Compliance guidance. Digit tables are from public explainers that agree with one another, and the IEC and BSI listings for IEC 60529 and IEC 62262 were read on 5 November 2026; the standards themselves were not. Confirm every digit and test value against the current edition. The location table gives starting points for the electrical engineer and lighting designer, not requirements. For bathrooms follow BS 7671 Section 701. Guidance, not electrical advice.

At a glance

CodeReads asDoes not tell youWhere you meet it
IP20Objects over 12.5 mm (a finger) kept out. No water protection.Anything about damp or dust.Decorative fittings for dry interiors (usual, unconfirmed).
IPX4Splashing water from any direction. Solids not rated.Dust, jets, immersion.The least for bathroom zones 1 and 2 (public guidance to BS 7671).
IP65Dust-tight. Water jets (6.3 mm nozzle).Immersion, salt, chemicals.Exposed terraces and hose-down areas.
IP67Dust-tight. Temporary immersion, up to 1 m for 30 minutes.Jets: IP67 does not imply IP65 or IP66.Fittings that may be briefly submerged.
IPX7Temporary immersion, up to 1 m for 30 minutes. Solids not rated.Dust, jets.The least for bathroom zone 0 (public guidance).
IK07 to IK10An enclosure that withstands 2 joules (IK07) up to 20 joules (IK10) of impact energy.Glass safety.Fittings within reach or in knock-prone areas (practice).

Digits from public explainers cross-checked against the IEC and BSI listings; the standards were not read. The last column is practice, except where it names the bathroom guidance.

Reading an IP code

IP, usually expanded as ingress protection, is a two-digit code defined by IEC 60529, Degrees of protection provided by enclosures (IP Code). The IEC lists the current consolidated edition as 2.2, IEC 60529:1989+AMD1:1999+AMD2:2013, published on 29 August 2013, and says it applies to enclosures of equipment rated up to 72.5 kV. BSI lists the British adoption, BS EN 60529:1992+A2:2013, as current (published 28 February 2019). We have not read either text. The digits below come from public explainers that agree with one another, and they should be confirmed against the standard.

  • The first digit, 0 to 6, is protection against solid objects, which also means against touching live parts.
  • The second digit, 0 to 9, is protection against water.
  • An X in either place means that characteristic was not rated. It does not mean zero: IPX4 says nothing about dust.
  • There are no hyphens in a standard code. Optional letters can follow the digits: ask the maker what any letter means.
  • Two ratings are written with a slash. IPX5/IPX7 means the enclosure passed both a jet test and an immersion test.
How to read an IP code and an IK code on a luminaire rating plateTwo rating-plate panels. On the left the code IP44 is split into IP, a first digit 4 for solids and a second digit 4 for water: solids over 1 millimetre are kept out, and splashing water from any direction is tolerated. On the right the code IK07 stands for an impact energy of 2 joules, on a scale that runs from IK00 to IK10, with IK11 added in 2021. Four chips along the bottom read common codes: IP20, fingers kept out and no water protection; IP44, wires kept out and splashing water; IP65, dust-tight and water jets; IP67, dust-tight and temporary immersion.IP44ingressprotectionsolidswaterIK07impactprotectionenergy levelFirst digit 4Solids over 1 mmkept out (wires)Second digit 4Splashing waterfrom any directionIK07 = 2 joules of impact energyThe scale runs IK00 to IK10 (IK11, 50 J,was added in 2021). It is not an IP digit.IP20Fingers kept out.No water protection.IP44Wires kept out.Splashing water.IP65Dust-tight.Water jets.IP67Dust-tight.Temporary immersion.
How to read IP44 and IK07, with four common codes. Original drawing by Make Bespoke Studio: the digits are from public explainers, so confirm them against IEC 60529 and IEC 62262.

The two digits, one at a time

The first digit is a ladder of probe sizes, ending in dust. Digit 1 means objects over 50 mm are kept out (the back of a hand), 2 means over 12.5 mm (a finger), 3 over 2.5 mm, 4 over 1 mm, 5 means dust protected (some dust may enter but not enough to interfere with safe working) and 6 means dust-tight. There is no 7, 8 or 9 for solids.

The second digit is not one ladder. Digits 1 to 4 are drips, spray and splashing, 5 and 6 are jets, 7 and 8 are immersion and 9 is hot, high-pressure jets. Public explainers say jets and immersion test different things, so passing the immersion test (7) does not imply passing the jet tests (5 or 6). That is why a fitting for a wet area is often marked with two ratings.

The IP code digits: solids 0 to 6 and water 0 to 9Two ladders side by side. The first digit, for solids, runs from 0 no protection through 1 objects over 50 millimetres, 2 over 12.5 millimetres, 3 over 2.5 millimetres, 4 over 1 millimetre, 5 dust protected, to 6 dust-tight. The second digit, for water, runs from 0 no protection through 1 vertical drips, 2 drips with the enclosure tilted 15 degrees, 3 spray, 4 splashing from any direction, 5 water jets, 6 powerful jets, 7 temporary immersion, 8 continuous immersion as agreed, to 9 high-pressure hot jets. Notes below the first ladder say that X means not rated rather than zero, and that jets and immersion test different things.First digit: solidsSecond digit: water0No protection1Over 50 mm (back of hand)2Over 12.5 mm (finger)3Over 2.5 mm (tools, thick wire)4Over 1 mm (wire, small screws)5Dust protected6Dust-tight0No protection1Vertical drips2Drips, enclosure tilted 15 degrees3Spray, up to 60 degrees from vertical4Splashing from any direction5Water jets (6.3 mm nozzle)6Powerful jets (12.5 mm nozzle)7Temporary immersion, up to 1 m, 30 minutes8Continuous immersion, as agreed9High-pressure hot jets (80 C)X in either place means not rated, not zero:IPX4 says nothing about solids.5 to 8 on the water scale test different things(jets, immersion): IPX7 does not imply IPX5.Letters such as K (IP69K) come from otherstandards, not from the IEC code itself.
The two IP digits as ladders. Original drawing by Make Bespoke Studio, with simple pictograms: not the test set-ups. Probe sizes and tests are from public explainers.

What the water tests do

What the water tests do, as the public explainers describe them (confirm against the standard):

Second digitWater test
1Vertical dripping water, enclosure on a turntable, 10 minutes.
2Dripping water with the enclosure tilted 15 degrees.
3Spray at up to 60 degrees from vertical.
4Splashing from any direction, by oscillating tube or spray nozzle.
5Water jets from a 6.3 mm nozzle at 12.5 litres a minute, at least 3 minutes.
6Powerful jets from a 12.5 mm nozzle at 100 litres a minute, at least 3 minutes.
7Temporary immersion, up to 1 m deep for 30 minutes.
8Continuous immersion, with depth and time agreed with the maker.
9High-pressure jets of water at 80 degrees C.

The tests use fresh water. A “K” suffix, as in IP69K, comes from other standards (DIN 40050-9 and ISO 20653 in the explainers), not from the IEC code itself.

What an IP rating does not tell you

An IP rating says how an enclosure behaves in a laboratory test. It leaves out a good deal that matters on a hospitality project.

  • Corrosion, salt and chemicals. The tests use fresh water. Salt water, oils and solvents are not covered, and the explainers we read list corrosion and chemical exposure among the things the code does not address. A fitting for a coastal terrace or a spa needs a material and finish chosen for the exposure: see metal by environment and metal finishes for luminaires.
  • Impact. IP is not an impact rating. That is the IK code below. (Before the IK code existed, a third numeral was sometimes added to an IP code, as in IP66(9).)
  • Other conditions. The explainers list icing, oil and coolant and hazardous atmospheres as outside the code. None of them mentions steam, condensation, sunlight or heat, so ask the maker rather than assume.
  • A higher number is not always better. For water, 5 and 6 test jets and 7 and 8 test immersion, and neither outranks the other.
  • The fitting as installed. A rating belongs to the fitting as tested. Ask what has to be done on site to keep it (seals, glands, canopy, driver position) and what would void it. A fitting with a remote driver or transformer has two enclosures: ask for the rating of each.
  • Glass. The IP and IK codes classify an enclosure. Whether a glass shade shatters, and how, is a separate question that neither code answers.

The IK scale: impact energy in joules

The IK code is a separate scale, defined by IEC 62262, Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code). It runs from IK00, not protected, to IK10, and each step is an impact energy in joules. Amendment 1 of 3 September 2021 added IK11, at 50 J. The IEC lists edition 1.0 of 12 February 2002 with that amendment; BSI lists BS EN 62262:2002+A1:2021 as current (31 October 2021) and shows the plain 2002 edition as withdrawn. We have not read the standard. The energies and test hammers below come from a public explainer. We checked that mass times 9.81 times drop height reproduces the energy for IK07 to IK11, but the explainer gives IK01 to IK05 only as a range, and public sources differ on hammer details, so confirm against the standard.

IK codeImpact energyTest mass and drop height
IK010.14 JEnergy only in the sources read
IK020.2 JEnergy only in the sources read
IK030.35 JEnergy only in the sources read
IK040.5 JEnergy only in the sources read
IK050.7 JEnergy only in the sources read
IK061 JEnergy only in the sources read
IK072 J0.5 kg dropped 0.40 m
IK085 J1.7 kg dropped 0.30 m
IK0910 J5 kg dropped 0.20 m
IK1020 J5 kg dropped 0.40 m
IK1150 J10 kg dropped 0.50 m

What the code means: the enclosure withstands that impact energy in the standard’s test, which strikes it with a hammer (five impacts, spread evenly, according to the explainer). It is a rating for the enclosure. Decorative glass fittings are generally not IK-rated, so do not assume an IK rating for glass: put a fitting that can be knocked out of reach, behind a guard, or specify one made for it.

The IK scale: impact energy from IK01 to IK11 in joulesEleven horizontal bars on a logarithmic scale, one for each IK code from IK01 at 0.14 joules to IK11 at 50 joules. IK11, added in 2021, is outlined with a dashed line. From IK07 upward a column gives the test mass and drop height that produce the energy: IK07 0.5 kilograms from 0.40 metres, IK08 1.7 kilograms from 0.30 metres, IK09 5 kilograms from 0.20 metres, IK10 5 kilograms from 0.40 metres and IK11 10 kilograms from 0.50 metres.CodeImpact energy in joules (log scale)Test mass and drop (IK07 and above)IK010.14 JIK020.2 JIK030.35 JIK040.5 JIK050.7 JIK061 JIK072 J0.5 kg dropped 0.40 mIK085 J1.7 kg dropped 0.30 mIK0910 J5 kg dropped 0.20 mIK1020 J5 kg dropped 0.40 mIK1150 J10 kg dropped 0.50 mIK11 was added by Amendment 1 (2021).Energy = mass x 9.81 x height. Masses and heights are from a public explainer: confirm against the standard.
The IK scale on a logarithmic axis, with the test mass and drop height from IK07. Original drawing by Make Bespoke Studio, from the energies in a public explainer; IK11 was added in 2021.

Which rating where: hospitality locations

These are starting points to put to the electrical engineer and the lighting designer. They are specification practice, not requirements from any document we read, except where a row says so. Square brackets mark values to confirm. For a bathroom, the rule is BS 7671 Section 701, set out in the bathroom zones sheet.

PlaceWhat reaches the fittingClosest IP testStarting point (practice; confirm)IK
Dry interior: lobby, restaurant, guestroomDust and a cleaning cloth.None needed.[IP20]. Decorative glass fittings usually sit here.Not usually stated for decorative fittings (unconfirmed).
Bathroom, outside the zonesSteam and splashes.Splashing (second digit 4).Section 701 sets no least IP (public guidance). NICEIC recommends splash-proof: [IP44].As dry interior.
Bathroom zones 0, 1 and 2Water from the bath or shower.Immersion (7) in zone 0; splashing (4) in zones 1 and 2.Least IPX7 in zone 0 and IPX4 in zones 1 and 2 (public guidance to BS 7671 Section 701): see the bathroom zones sheet.Not applicable.
Spa wet area, steam room, pool hallSplashes, hot humid air, chlorinated or salt water, cleaning chemicals.Jets (5 or 6) at most. The code does not test the air or the chemistry.Ask the engineer: BS 7671 has separate rules for pools and saunas (not read). [IP65 or higher], with material and finish chosen for the chemistry.[IK07 or higher] where guests or staff can knock it.
Commercial kitchen, scullery (back of house)Grease, steam, hose-down, knocks from trolleys.Jets (5 or 6).[IP65][IK08 to IK10]
Back-of-house corridor, store, plant roomDust, trolleys, mops.Dust (5 or 6) and splashing (4).[IP54 to IP65][IK08 to IK10]
Covered terrace or entranceWind-blown rain, insects, dust.Splashing (4) and dust (5).[IP44 to IP54][IK07] where reachable
Open terrace, garden, car parkRain, hose cleaning, sun and frost.Jets (5). The code does not test sun or frost.[IP65][IK08 to IK10] where reachable
Coastal or marineSalt spray.None: the IP tests use fresh water.[IP65 or higher], with a marine-suitable metal and finish: see the metal by environment sheet.As above.

Decorative glass chandeliers are typically IP20, for dry interiors only. Do not specify one for a terrace, a spa, a kitchen or a bathroom zone. Ask the partner workshop what it can make or supply to the rating the place needs, and have the rating stated per fitting, in writing.

What to ask for on a rating plate or data sheet

  • The IP rating of each fitting type, on the data sheet and on the rating plate, and the IK rating where a fitting can be knocked. See the luminaire data sheet to demand, field E3.
  • The configuration tested: with the glass or shade fitted, with the cable gland and canopy as supplied, on the mounting surface the maker states.
  • What changes the rating: drilling, a different gland, a substitute lamp holder, a different driver position, a missing seal.
  • The rating of the driver or transformer if it is separate, and where it is to be sited.
  • The test evidence: who tested, to which standard and edition, and whether the report covers this fitting. See the conformity sheet.
  • The environment the maker intends: in words, for example “dry interiors only”, so the rating is not read as more than it is.

Specification wording

Paste into your schedule or specification and replace anything in [square brackets] with your own figures. Wording is a starting point: your specification governs.

IP and IK statement
The supplier states for each luminaire type, on the data sheet and the rating plate, the IP rating [IP20 / IP44 / IP65] under BS EN 60529 [edition] and, where a fitting can be knocked, the IK rating under BS EN 62262 [edition and amendment], with the configuration tested (shade fitted, gland and canopy as supplied, mounting) and what would change it.
Location minima
Luminaires in [location] are rated at least IP[ ] and IK[ ], as the luminaire schedule. The supplier confirms the rating applies as installed, lists any site step that would void it, and states the rating and position of any separate driver.
Fittings not rated for damp
Fittings rated IP20, or with no IP rating stated, are installed only in dry interiors, outside bathroom zones 0, 1 and 2. The supplier states in writing the environment each fitting is made for.
Corrosion
An IP rating does not cover corrosion. For [coastal / spa / pool-hall] locations the supplier states the base metal, finish and exposure suitable, apart from the IP rating.

Terms used on this page

IP rating
A two-digit code for how well an enclosure keeps solids (first digit) and water (second digit) out. An X means not rated, not zero.
IK rating
A scale from IK00 to IK10 (IK11 since 2021) for the impact energy an enclosure withstands, in joules.

All lighting terms

Standards and sources

Questions we are asked

What does IP stand for in lighting?

IP is usually expanded as ingress protection. It is the code from IEC 60529 that says how well an enclosure keeps out solid objects (first digit, 0 to 6) and water (second digit, 0 to 9). Older sources expand it as international protection. Confirm the wording against the standard.

What does the X mean in IPX4?

The X means the first characteristic, protection against solids, was not rated. It does not mean zero. IPX4 only says the enclosure resists splashing water from any direction, and says nothing about dust.

What is the difference between IP44 and IP65?

IP44 keeps out objects over 1 mm and tolerates splashing water. IP65 is dust-tight and tolerates water jets from a 6.3 mm nozzle, so it is a much tougher rating for a terrace or a hose-down area. Both are about water and dust only: neither covers salt or chemicals.

Is IP67 better than IP65?

Not simply. IP67 means temporary immersion and IP65 means jets, and public explainers say passing one does not imply passing the other. A fitting that must survive both needs both ratings, written IPX5/IPX7 or IP65/IP67.

What IP rating do I need for an outdoor light?

It depends on the exposure. A covered terrace sees wind-blown rain, an open terrace sees rain and hose cleaning, and a coastal one sees salt that the IP tests do not cover. Starting points are in the table above, in square brackets: confirm them with the electrical engineer and lighting designer.

Do chandeliers have an IP rating?

Yes, every luminaire has one, but a decorative glass chandelier is typically IP20, which means fingers kept out and no water protection, so it is for dry interiors only. The maker must state the actual rating of each fitting in writing, and what would change it.

What does an IK rating mean?

IK is a separate scale from IK00 to IK10 (IK11 since 2021) for how much impact energy an enclosure withstands in the standard's test, from 0.14 joules at IK01 to 20 joules at IK10 and 50 joules at IK11. It is a rating for the enclosure and says nothing about whether glass would shatter safely.

Can I use an IP20 chandelier in a bathroom?

Not in zones 0, 1 or 2, which need at least IPX7 or IPX4 according to public guidance to BS 7671 Section 701. Wholly outside the zones the guidance sets no least IP rating, but steam and cleaning remain: see the bathroom zones sheet and have the electrical engineer confirm.