At a glance
| Item | What to settle | Basis |
|---|---|---|
| Lighting points | Give every point in the room its own circuit or channel, so a scene can set each one. | Practice |
| Scenes | Five to seven, named for what the guest is doing (arrival, relax, read, work, sleep, night), and one for housekeeping. | Practice; trade press |
| Master off, plain switch | One all-off at the bed and one at the door; sleep means everything off. Keep a physical switch for the main light. | Practice; trade press |
| Occupancy control | Key-card switch or presence detection that turns lights off when the room is empty. | Approved Document L vol 2, 2026 ed., 5.70 |
| Control heights | Precise controls 750 to 1,200 mm; push buttons up to 1,200; sockets 400 to 1,000. | Approved Document M vol 2, 4.30 |
| Night path | Low level and short. Have an access consultant review any low or floor-level uplight. | Approved Document M vol 2, 4.34; practice |
| Colour and dimming | 2700 K or below where people sleep. Settle the dimming method before the fittings are ordered. | Our hotel lighting article; TL-LIG-04, TL-LIG-07 |
| Serviceability | Light sources and drivers replaceable with common tools; drivers reachable; spares; a care sheet. | SI 2021/1095 reg 6(1); practice |
The scenes, their number and their levels are our checklist, not a standard. The only regulated statements are the Approved Document L and M paragraphs named.
The room as nine lighting points
A guestroom has fewer lighting points than a lobby but more jobs. The plan numbers nine: the entry, a wash on the bedhead wall, a reading light each side of the bed, a desk lamp, the wardrobe, the bathroom mirror and general light, and a low-level night path from the bed to the bathroom door. Not every room has all nine, and the plan is a layout, not a recommendation.
- One circuit or channel per point. A scene can only set what is controlled separately. The two reading lights are two points, so each side of the bed can read without the other.
- Count the fittings on each circuit and write the number on the schedule. A point with several fittings has to dim together, which is a driver question: see dimming protocols for decorative lighting.
- The bathroom has its own rules. It has a local switch or presence sensor, often a separate switch for the mirror light, and the zone and IP rating of every fitting in it come first. Mirror light heights are on the wall light heights sheet.
Seven scenes, and a rule for naming them
Scenes only help if the guest can find them and the names mean something. The matrix is a starting set for the lighting designer: seven scenes against the lighting points, with the size of each dot showing a relative level. It is not in lux. None of the documents we read gives lux for a hotel guestroom (see lighting levels by space), so levels are set in a sample room, not read off a table.
- Name scenes for what the guest is doing, in words and icons: arrival, relax, read, work, sleep, night. Housekeeping is not a guest scene: it gives full light for cleaning and maintenance.
- Sleep is everything off, one touch from the bed. Night is a low-level path and a dim bathroom light for the walk across the room.
- Keep the reading lights separate. Each side has its own control, so one person can read while the other sleeps.
- Warm light wherever people sleep: 2700 K or below, with cleaner light kept for the bathroom mirror, as in our hotel lighting design article. See colour temperature by space for the sources.
What the evidence says, and how little. Hotel designers in a 2021 trade-press round table say that in a hotel room the control should be with the guest, that guests miss having a physical switch, and that controls need to be simple yet intelligent. The only field study of guest use we found is a US national laboratory study of ten rooms in one hotel, logged for three months in 1998, when rooms used filament lamps: bathroom lights were on for about eight hours a day and bed-end lamps for nearly five, fewer than 15 per cent of lights were on between midnight and 5 am, and the team trialled a bathroom night light at 10 per cent output. It shows where use concentrates, not what guests want today.
Control points: what, where and how high
Where a control sits matters as much as what it does: it is found in the dark, half awake, by someone who has not seen the room before. Heights below are from Approved Document M volume 2 (2015 edition incorporating 2020 and 2024 amendments), which governs buildings other than dwellings in England; which of them applies to a given guest control is for the building control body or an access consultant. The wall light sheet draws them on a bedhead wall.
| Control point | What it does | Where, and how high | Basis |
|---|---|---|---|
| Inside the door | Key-card holder or presence detection: lights off when the room is empty; entry light and arrival scene on. | Light switches for the general public: large push pad, aligned horizontally with the door handles, 900 to 1,100 mm; where that is not possible, a pull cord 900 to 1,100 with a 50 mm contrasting bangle. | ADL 2026 5.70; ADM vol 2 4.30(h), (i) |
| Bedside, each side | Reading light on, off and dim; one master off; one or two scene buttons (relax, night). | Controls needing precise hand movement 750 to 1,200 mm; simple push buttons not more than 1,200; sockets 400 to 1,000. No two-handed operation, contrasting plates, no red and green together as on and off. | ADM vol 2 4.30(a), (c), (d), (j), (m); 4.28 |
| Desk | Desk lamp switch, on the lamp or on a desk panel. | On the lamp itself, or within reach of a seated user. | Practice |
| Wardrobe | Light switched by the door or by a presence sensor, so it does not stay on with the door shut. | Position set by the joinery drawing. | Practice |
| Bathroom | Local switch or presence sensor; mirror light on its own switch; low-level night light. | Zone and IP rating first (BS 7671 section 701, not read). | Practice; one US field study |
| Accessible bedroom | The same, plus an emergency assistance pull cord reachable from the bed and from the floor beside it. A lighting cord must not be mistaken for it. | Emergency cord: red, two red 50 mm bangles, one at 100 and the other 800 to 1,000 mm. Lighting cord bangle visually distinguishable from it. | ADM vol 2 4.24(q), 4.30(e), (i) |
| Night path | Low-level light from the bed to the bathroom, on the night scene or a sensor. | Paragraph 4.34 says uplighters mounted at low or floor level can disorientate some visually impaired people and should be avoided. It speaks of uplighters: the access consultant decides how it applies to a path light. | ADM vol 2 4.34 |
Where Part L meets the guestroom
Approved Document L volume 2 for England has a paragraph written for this room. In the 2026 edition, paragraph 5.70 (page 56) says that in hotel bedrooms, controls such as key-card switches and/or controls that automatically detect occupation should be installed to turn off internal lights during unoccupied periods. That edition takes effect on 24 March 2027 for building work that is not in connection with higher-risk building work, and on 24 September 2027 for higher-risk building work; transitional arrangements apply and are set out in Circular Letter 01/2026, which we did not read for this sheet.
The 2021 edition (page 53) has no hotel-bedroom paragraph. Its controls paragraphs 6.62 to 6.65 point to Building Research Establishment Digest 498, ask for automatic controls that turn general lighting off in unoccupied spaces, ask for daylight controls in occupied spaces, and ask for display lighting on separate circuits. ‘Should’ marks guidance, not regulation. How the efficacy limits meet decorative fittings is on the Part L and chandeliers sheet.
Serviceability: questions for the partner workshops
Put these to the partner workshop before the shop drawings are approved. Hotels pay for a fitting that cannot be re-lamped, cleaned or repaired in place for the whole life of the room.
- Replaceable light sources and drivers. For a ‘containing product’, regulation 6(1) of the Lighting Products Regulations 2021 (SI 2021/1095) asks manufacturers and importers to ensure light sources and separate control gear can be replaced with commonly available tools and without permanent damage, unless a technical justification is in the documentation (6(2)), and to publish whether they are replaceable (6(4)). Whether it bites on a bespoke fitting made for one room is for product-compliance advice. Ask for the statement either way.
- Standard drivers and lamp bases, named on the schedule, so the same part can be bought later (see the luminaire data sheet sheet).
- Reach. A bedside wall light is re-lamped from a stool, not a ladder, and its driver sits where a maintenance person can reach it, not behind a fixed headboard panel without an access hatch.
- Spares. Spare drivers, and spare touch-point parts in the same finish batch (see metal finishes for luminaires).
- Labels and records. A circuit and scene schedule in the handover file, the dimming pairing tried and signed off, and a care sheet for each finish.
- A sample room. Build one room completely, set and sign off the scenes there, and only then roll out.
Specification wording
Paste into your schedule or specification and replace anything in [square brackets] with your own figures. Wording is a starting point: your specification governs.
Guestroom lighting to comprise [nine] lighting points as the room plan [drawing ref]: [entry, bedhead wash, reading light left and right, desk lamp, wardrobe, bathroom mirror, bathroom general, night path]. Each point on its own [circuit / DALI group / channel], with [ ] fittings per point. The lighting designer's schedule [ref] governs levels, colour temperature [2700 K or below where people sleep] and dimming range.
Scenes [arrival, relax, read, work, sleep, night, clean] as the scene matrix [ref], set in the sample room by [controls supplier] with [lighting designer] and signed off by [operator]. One master off at the bedside and at the door; each reading light on its own control; a physical switch for [the main light]. [Key-card or presence control to switch lights off when the room is empty (Approved Document L volume 2, 2026 edition, 5.70).] Control plates within Approved Document M volume 2, paragraph 4.30 ([edition]), accepted by [body].
Light sources and drivers replaceable with commonly available tools without damage to the fitting, or a technical justification supplied; driver type, part number and location on the schedule. [ ] spare drivers and [ ] sets of touch-point parts per [ ] rooms, same finish batch. Handover: circuit and scene schedule, driver data sheets, care sheet by finish, sample room sign-off.
Terms used on this page
- Scene
- A stored lighting setting that sets several circuits to chosen levels at once, such as 'relax' or 'sleep', recalled by one button.
- Key-card switch
- A holder inside the door that takes the room key card and switches the room's lights on when the card is in, and off when it is taken out.
Standards and sources
- Approved Document L volume 2 (England): 2026 edition and 2021 edition incorporating 2023 amendments: read: 2026 edition statement and 5.64 to 5.72 (pp.55 to 56); 2021 edition 6.60 to 6.65 (p.53).
- Approved Document M volume 2 (England), 2015 edition incorporating 2020 and 2024 amendments: read: 4.24, 4.28 to 4.30, 4.34 (pp.43 to 45).
- SI 2021/1095 regulation 6; LBNL-44448 (US DOE laboratory, 1999): regulation read in full; one US hotel, ten rooms, 1998.
- BRE Digest 498, SLL Code for Lighting 2022, CIBSE LG14, BS 8300-2:2018: named only; not read.
Questions we are asked
How many lighting scenes does a hotel bedroom need?
No standard says. Our starting set is six guest scenes (arrival, relax, read, work, sleep, night) and one for housekeeping. Fewer is easier: trade-press designers say controls should be simple, and that guests miss a plain switch. Test the set in a sample room before it is rolled out.
Do hotel bedrooms need key-card switches?
In the 2026 edition of Approved Document L volume 2 (England), paragraph 5.70 says controls such as key-card switches and/or controls that detect occupation should be installed to turn off internal lights during unoccupied periods. The edition takes effect on 24 March 2027 for most work, with transitional arrangements in Circular Letter 01/2026. It is guidance, and the 2021 edition has no such paragraph.
How high should bedside controls be?
Approved Document M volume 2, paragraph 4.30, gives 750 to 1,200 mm for controls that need precise hand movements, up to 1,200 mm for simple push buttons and 400 to 1,000 mm for sockets. Which apply to a given guest control is for building control or an access consultant. See the wall light heights sheet.
What lux level should a hotel bedroom have?
None of the documents we read gives one. CIBSE's guide to communal residential lighting says it does not cover hotels, that hotels generally have their own corporate lighting specification, and points to a chapter of the SLL Lighting Handbook (2012) that we have not read. The lighting designer sets levels in a sample room, against the operator's specification.
Should the night path be on a sensor?
No source we read settles it. Approved Document M paragraph 4.34 says uplighters mounted at low or floor level can disorientate some visually impaired people and should be avoided, so an access consultant should review a floor-level light. Try both a scene and a sensor in the sample room.
Why do guests complain they cannot find the main light?
Trade-press designers say guests miss a physical switch. Keep one obvious, plainly labelled control for full light, even where the scenes are run from a screen or keypad.