Compliance guidance. Figures are taken from the editions named, for England, read on 5 November 2026. Check the current editions, Scotland, Wales and Northern Ireland, and your building control body. This is guidance, not legal or engineering advice: fire, sound and access questions are for a fire engineer, an acoustician and an access consultant.

At a glance

CheckSettleAsk forWhat the rules say
1 WearSpecies, construction and, for engineered boards, the wear layer above the tongue and groove.The maker's written statement of intended use, wear layer depth and a hardness figure for the species.No wear class for timber floors in the three Approved Documents read.
2 FinishLacquer, oil or hardwax oil; sheen; who cleans and refreshes it, and how often.Finish data sheet, cleaning and refreshing instructions, a sample finished as the floor will be.None. Our wood floor finishes guide: lacquer is the most resistant to spills and traffic; oil can be refreshed in worn areas.
3 SlipPendulum value wanted, wet, on the finished floor, and who tests it.A wet pendulum (BS 7976) report on the finished sample.HSE: 36 or more is low slip potential. Approved Document B 5.17 and Approved Document M 3.14(k) ask for slip-resistant finishes.
4 AccessThresholds, level changes, contrast with walls, floor patterns.Threshold details on the drawings; light reflectance values of floor and walls.Approved Document M: threshold level or 15 mm at most; light reflectance difference of more than 30 points.
5 SoundImpact build-up under the floor and who proves it; absorption in corridors.Test evidence for the whole build-up; a pre-completion test plan.Approved Document E: hotel rooms, impact 62 dB L'nT,w at most (purpose built); corridors need added absorption.
6 FireThe reaction-to-fire class the fire strategy, insurer or operator wants.The declared class to BS EN 13501-1, in writing, for the floor as laid.England, Approved Document B: B2 gives no guidance on the upper surfaces of floors.
7 HeatUnderfloor heating or not; the maker's maximum surface temperature; commissioning.The heating engineer's commissioning record and the maker's approval of the build-up.No Approved Document figure. See our underfloor heating sheet for the makers' 27 °C.
8 UpkeepDaily cleaning, entrance matting, refreshing cycle, closures.A maintenance manual and the list of approved products.None. HSE: slip resistance changes with cleaning, polishing and wear.
9 RenewalHow many times it can be sanded, how a worn area is repaired, spare stock.Number of sands the wear layer allows; a repair method; spare boards from the same batch.None. See solid vs engineered for the sanding arithmetic.

England. Approved Documents B, E and M and the HSE sheet were read on 5 November 2026; see the rules table below. The partner flooring workshop confirms what it supplies for commercial use.

The tick-sheet

A busy timber floor goes wrong in a handful of predictable ways, and each has a question for the designer and a piece of evidence to ask the maker for. The tick-sheet lists nine. Tick each box when the item is written into the specification and its evidence is in hand. The table below turns each box into the question, the evidence and what the rules say about it.

Most of the boxes have no number in a standard. Where a number appears it comes from a document we read, with the edition named, and England is assumed. The numbers are the rules' limits, not a design target.

Tick-sheet for a timber floor in a hotel, restaurant or other busy interiorA sheet of nine ticked boxes in three rows of three: wear, finish, slip, access, sound, fire, heat, upkeep and renewal, each with a short prompt. Tick each box when the item is specified and its evidence has been received.Timber floor, busy interior: tick-sheetTick when specified and the evidence is in hand1 Wearspecies, wear layer, build2 Finishlacquer or oil, sheen3 Slipwet pendulum test4 Accessthresholds, contrast5 Soundfloors and corridors6 Fireclass stated in writing7 Heattemperature, commissioning8 Upkeepcleaning and refreshing9 Renewalsanding, repair, spares
Nine boxes to tick for a timber floor in a busy interior. Original drawing by Make Bespoke Studio.

What the rules say, and what they leave out

Few of the nine checks have a figure in the Approved Documents, and one important check has none at all. The table sets out what the three Approved Documents and HSE say, quoted where the wording matters. The editions are in the standards list.

TopicDocument and paragraphWhat it saysWhat it leaves out
Fire, floor surfaceApproved Document B volume 2, Requirement B2, ‘Intention’‘Requirement B2 does not include guidance on’ ... ‘the upper surfaces of floors and stairs.’ Appendix B (B6) classes products ‘other than floorings’ A1 to F, so floorings have their own classes.So the Approved Document gives no floor fire class for England. Scotland, Wales, Northern Ireland, the fire strategy, the insurer and the operator may: not read.
Escape route slipApproved Document B volume 2, paragraph 5.17‘Escape route floor finishes should minimise their slipperiness when wet.’No figure.
Slip valuesHSE, Assessing the slip resistance of flooring, Table 1 (UKSRG 2011)Pendulum test value 0 to 24 high slip potential, 25 to 35 moderate, 36 or more low. HSE's standard test is the pendulum (BS 7976).The sheet gives bands, not a required value. HSE warns that makers' data are usually as supplied and can change after installation, cleaning, polishing and wear.
ThresholdsApproved Document M volume 2, paragraph 2.7(e), (h)Threshold level or, if a raised threshold is unavoidable, 15 mm at most, with upstands over 5 mm chamfered or rounded. Changes in floor material should not create a trip hazard.Written for accessible entrances; the paragraphs for other level changes were not summarised.
Corridor floorsApproved Document M volume 2, paragraph 3.14(j), (k)Avoid floor patterns that could be mistaken for steps or changes of level. Floor finishes are slip resistant.No slip value.
Visual contrastApproved Document M volume 2, interpretation of ‘contrast visually’Light reflectance value (LRV) difference greater than 30 points; at least 20 points where illuminance on the surfaces exceeds 200 lux; 15 points for door furniture.Which surfaces must contrast is set element by element in the document.
Impact soundApproved Document E, Table 0.1bRooms for residential purposes (the category that covers hotel rooms): separating floors and stairs, impact L'nT,w 62 dB at most if purpose built, 64 dB at most if formed by change of use.Para 0.8: a higher standard may be needed next to communal or non-domestic spaces, and specialist advice is needed.
CorridorsApproved Document E, Section 7 (7.10, 7.18)Requirement E3: corridors giving access to rooms for residential purposes need added absorption: Method A covers an area at least the floor area with a Class C absorber or better; Method B gives at least 0.25 m² of absorption area per m³ of corridor.The calculation is the acoustician's.

England only. The documents were read on 5 November 2026. Approved Document E prints its tables as 0.1a and 0.1b in the text and 1a and 1b in some cross-references; the figures are the same. Check the current editions and your building control body, and use the specialist (fire engineer, acoustician, access consultant) for anything that is not a plain number.

Sound in a hotel: three questions about one floor

Sound is the check that surprises designers most on a timber floor. There are three separate questions.

  • The floor between rooms. Approved Document E Table 0.1b sets impact sound for the floors and stairs that separate rooms for residential purposes, which the document says covers hotel rooms: 62 dB L'nT,w at most for purpose-built rooms and 64 dB for rooms formed by a change of use. The lower the figure the better. Impact tests are made on the floor without a soft covering, except for separating floor type 1 and for a base with an integral soft covering (Annex B, B2.13). Type 1 is described as a concrete base with a ceiling and a soft floor covering, so, as we read it, a timber floor in place of carpet no longer matches that type. The floor then needs a tested design, such as a floating layer, and a plan for pre-completion testing. That is for the acoustician.
  • The neighbouring use. Paragraph 0.8 says the table values suit spaces used for normal domestic purposes, and that a higher standard may be needed between those and communal or non-domestic spaces, such as a restaurant or bar under bedrooms. It asks for specialist advice.
  • The corridor. Requirement E3 applies to corridors, stairwells, hallways and entrance halls that give access to rooms for residential purposes. A hard timber floor adds little: in the document's table of typical absorption coefficients, a parquet or lino floor on concrete absorbs 0.05 at 1,000 Hz where carpet absorbs 0.15 (and 0.40 against 0.06 at 4,000 Hz). So the absorption has to come from the ceiling or the walls. Method A covers an area at least equal to the floor area with a Class C absorber or better, and Method B asks for at least 0.25 m² of absorption area per m³ for a corridor.
Surface (Approved Document E, Table 7.1)250 Hz500 Hz1,000 Hz2,000 Hz4,000 Hz
Hard floor covering, such as parquet, on concrete0.030.040.050.050.06
Soft floor covering, such as carpet, on concrete0.030.060.150.300.40
Glazed tile or marble0.010.010.010.020.02

Typical sound absorption coefficients from Approved Document E, Table 7.1 (octave bands). A higher figure absorbs more.

Wear, finish, upkeep and renewal

Wear, finish, upkeep and renewal are one decision made four ways, so settle them together and write the regime into the specification.

Wear. We found no wear class for timber floors in the three Approved Documents, so the evidence is the maker's: its stated intended use in writing, the species and a hardness figure for it, and for an engineered board the depth of wear layer above the tongue and groove, which sets how many times the floor can be sanded. The arithmetic is on solid vs engineered wood flooring. The grade of the timber is about appearance, not strength: see wood flooring grades.

Finish. Our wood floor finishes guide compares the two main families. A lacquer forms a hard, sealed film, is the most resistant to spills and heavy traffic and is cleaned, not fed; a repair means sanding and recoating, so it is harder to hide. An oil soaks in, can be refreshed and repaired in worn areas without sanding the whole floor, and takes a maintenance oil from about once a year to every two to four years depending on the product and the traffic. The guide says neither is better in itself. Choose by the room and by who will look after it.

Slip and upkeep. HSE warns that makers' slip data are usually produced from the product as supplied, and that the slipperiness of a floor can change significantly with installation, cleaning, burnishing or polishing, and after short periods of use. Ask for the pendulum result on the finished sample, and keep the cleaning regime the same as the one tested. Grit is what wears a finish, so entrance matting, regular sweeping and felt pads under furniture do most of the work.

Renewal. Plan the first refinish before the floor is laid: the interval, who does it, whether a worn area is touched in or the whole floor is sanded, and what stock is kept. Ask for spare boards from the same batch, since colour can differ between batches (see the grades sheet). The suggestion is ours, not a standard.

Heat, transitions and handover

Heat. Over underfloor heating the floor maker's maximum surface temperature, the commissioning and the build-up all need agreeing: see underfloor heating under wood and stone. Subfloor and site. A big floor in a new building is only as good as the screed beneath it and the conditions around it: see subfloor requirements and acclimatisation and site conditions. Transitions. Where the timber meets another floor or a door, the threshold rules above apply, and the movement joint sets how the junction behaves: see floor transitions and movement joints.

Handover. Ask for a pack the operator can keep: the maker's statement of intended use, the finish data sheet and maintenance manual, the wet pendulum report, the declared reaction-to-fire class, the underfloor heating commissioning record, the acoustic test or design evidence, the retained approved sample, and the spare stock. Our partner flooring workshop confirms what it supplies for commercial use and the evidence it holds; this sheet does not say what any partner supplies.

Specification wording

Paste into your schedule or specification and replace anything in [square brackets] with your own figures. Wording is a starting point: your specification governs.

Wear and build
Timber floor for [hotel restaurant] use: [engineered oak, [ ] mm overall, wear layer [ ] mm above the tongue and groove, multi-layer core]; species and [hardness figure] stated by the maker, with the maker's written statement that the product is suitable for [commercial] use at this location.
Slip
Floor surface as finished to achieve a pendulum test value of [36] or more, wet, [Slider 96 rubber; Slider 55 where barefoot], to BS 7976, tested on [a finished sample / in situ] before [approval / handover]. The report is to state the finish and the cleaning regime used in the test.
Sound and fire
Floor build-up to achieve impact sound insulation of not more than [62] dB L'nT,w [purpose built rooms for residential purposes] where it separates [ ], shown by [pre-completion testing / the acoustician's design]. Corridor absorption to Approved Document E [Method A / B], by [the acoustic consultant]. Reaction-to-fire class of the floor as laid to be declared to BS EN 13501-1 and agreed with [the fire engineer]: [ ].
Upkeep and renewal
Maker to issue a maintenance manual (daily cleaning, matting, refreshing interval, approved products), the number of sanding cycles the wear layer allows, a repair method statement, and [ ]% spare boards from the same batch, delivered [with the floor].

Terms used on this page

Room for residential purposes
A building-regulations category, which includes hotel bedrooms and hostels, that is subject to Part E sound insulation targets.
Pendulum test value (PTV)
The result of a swinging-rubber-foot test (BS 7976) used to rate how slippery a floor is; UKSRG bands are 0-24 high, 25-35 moderate and 36 or more low slip potential.
L'nT,w
The weighted, standardised impact sound level measured in the room below a floor; lower is better, and Approved Document E sets a maximum of 62 dB for new-build floors and 64 dB for conversions.
Light reflectance value (LRV)
The percentage of visible light a surface reflects, used to compare how well adjacent surfaces contrast for people with sight impairment.

All flooring terms

Standards and sources

Questions we are asked

Does a timber floor in a hotel need a fire rating in England?

Approved Document B volume 2 says Requirement B2 does not include guidance on the upper surfaces of floors and stairs, so it gives no floor fire class for England. A class can still be asked for by the fire strategy, the insurer, the operator, or the rules in Scotland, Wales and Northern Ireland, which we have not read. Ask the maker for its declared class to BS EN 13501-1 and agree the requirement with the fire engineer.

What impact sound must a hotel bedroom floor meet?

Approved Document E Table 0.1b, for rooms for residential purposes, which includes hotel rooms, gives 62 dB L'nT,w at most for separating floors in purpose-built rooms and 64 dB for rooms formed by a change of use; lower is better. The floor is tested on site, without a soft covering for most constructions. A timber floor needs a tested build-up, and a restaurant or bar below may need more: ask an acoustician.

Does the corridor need acoustic treatment?

In a building with rooms for residential purposes, yes, under Requirement E3. Approved Document E asks for added absorption in corridors, by covering an area at least equal to the floor area with a Class C absorber (Method A) or by providing at least 0.25 m² of absorption area per cubic metre (Method B). A hard timber floor absorbs little, so the ceiling does the work.

How slippery can a restaurant floor be?

HSE reads a pendulum test value of 36 or more as low slip potential, 25 to 35 as moderate and 24 or under as high. Test the finished floor wet, with the finish and cleaning regime it will have in use, because HSE warns that makers' as-supplied data can change after installation, cleaning, polishing and wear. The Approved Documents ask for slip-resistant finishes but give no value.

What is the commercial rating for a timber floor?

We found no wear class for timber floors in Approved Documents B, E or M, and no single commercial grade like those used for some other floor types. The evidence is the maker's written statement of intended use, the species and its hardness, and for engineered boards the wear layer depth. Ask the partner flooring workshop what it supplies for commercial use.

Oil or lacquer for a restaurant?

Our wood floor finishes guide says neither is better in itself. Lacquer is the most resistant to spills and heavy traffic and is cleaned, not fed. Oil can be refreshed and repaired in worn areas without sanding the whole floor, but needs a maintenance oil from about once a year to every two to four years. Choose by who will look after the floor.

Can a hotel floor have underfloor heating?

Yes, with the maker's approval of the build-up and the heating, a floor surface limit (UK makers quote 27 °C), commissioning before fitting and a gradual restart afterwards. See our sheet on underfloor heating under wood and stone.

Download the factsheet

A two-page A4 PDF with the nine-box checklist, what the rules say, and specification wording, to keep with your project file.

Factsheet TL-FLO-11 v1.0 (PDF)