At a glance

RatingWhat it isWhere definedWhat to remember
Practical sound absorption coefficient, αpAbsorption in each octave band, 0 to 1, from reverberation-room test data (third-octave values averaged to octaves, rounded to 0.05, capped at 1.00)BS EN ISO 11654, clause 4.1The full curve. Ask for it; it is the most useful thing on a report.
Weighted coefficient, αwOne number, 0 to 1: the shifted reference curve read at 500 HzBS EN ISO 11654, clause 4.2Hides the shape of the curve. Rating starts at 250 Hz, so it says nothing below that.
Shape indicator L, M, HLetter(s) after αw where a band exceeds the shifted curve by 0.25 or more: L at 250 Hz, M at 500 or 1,000, H at 2,000 or 4,000BS EN ISO 11654, clause 4.3A warning that the product is much better in one range than its single number suggests.
Absorber class A to EA banding of αw for informationBS EN ISO 11654, Annex B (not read)Class limits are not given here: read the standard.
NRC and SAAUnited States single numbers, averages of tested bandsASTM C423 (not read)Not the same as αw: do not swap them.
RwHow much sound a wall or door blocks. Insulation, not absorptionBS EN ISO 717-1 (not read)Different question. See our acoustic doors sheet.

Clause references are to ISO 11654:1997, read in full in a publisher's free preview; Annexes B and C were not in it. NRC, SAA and Rw rows are pointers: no figures from those standards appear on this sheet.

Absorption is not insulation

A slatted or perforated timber panel is often chosen to make a room less echoey. That is absorption: it reduces reverberation inside the room by soaking up sound that reaches the surface. It is not insulation, which is how much sound passes through a wall or door (the Rw rating on our acoustic doors sheet). A panel that absorbs well can be a poor insulator, and the other way about.

Absorption is measured by putting a sample of the assembly in a reverberation room and timing how the sound decays. BS EN ISO 354:2003 is the measurement standard, which a trade listing summarises as a method for the sound absorption coefficient of materials used as wall or ceiling treatments; it is listed by BSI as current, under review. The result is a coefficient between 0 (all reflected) and 1 (all absorbed) in each frequency band. A test report belongs to the assembly as it was mounted: slats, gap, felt, backing and air space together. It does not belong to the timber.

How αw is found and what it hides

The standard rates absorption with one number so that a specification can set a target. The steps are worth knowing because they show what the number hides.

  1. The test gives a coefficient at each one-third-octave band. Each three are averaged into an octave band, rounded to the nearest 0.05, and capped at 1.00. These are the practical coefficients, αp (clause 4.1).
  2. A fixed reference curve is laid over the bands from 250 Hz to 4,000 Hz. Its unshifted values in the standard’s Figure 1 are 0.80 at 250 Hz, 1.00 at 500, 1,000 and 2,000 Hz, and 0.90 at 4,000 Hz.
  3. The curve is moved down in steps of 0.05 until the sum of the amounts by which the product falls below the curve is 0.10 or less. Amounts above the curve do not count (clause 4.2).
  4. αw is the value of the shifted curve at 500 Hz.
  5. If any band is 0.25 or more above the shifted curve, a letter is added in brackets: L if it is at 250 Hz, M at 500 or 1,000 Hz, H at 2,000 or 4,000 Hz (clause 4.3). The standard says to add a sentence recommending the full curve be used with the number.

Worked example from the standard. Annex A gives an absorber with practical coefficients of 0.20, 0.35, 0.70, 0.65, 0.60 and 0.55 in the 125 to 4,000 Hz bands. Shifting the curve down by 0.40 puts it at 0.40, 0.60, 0.60, 0.60 and 0.50 for 250 to 4,000 Hz; the only shortfall is 0.05 at 250 Hz, so αw = 0.60. At a shift of 0.35 the shortfalls total 0.15, which is too many. A second absorber, identical except for a coefficient of 1.00 at 500 Hz, gets the same αw of 0.60, but with an M added, because its 500 Hz value is 0.40 above the curve. Two products with the same number can behave very differently, which is why the standard says to use the number with the full curve. The drawing shows the second case.

What the standard says it is for. The single number can be used for products in routine applications in normal offices, corridors, classrooms and hospitals. It is not appropriate in qualified environments needing careful acoustic design, where only complete absorption data are satisfactory. It does not apply unless the application covers the whole range of the reference curve, it is not appropriate below 250 Hz, and it is often not suitable for single items such as chairs and baffles (clause 1.2).

Reading a single number: alpha-w and the shifted reference curveBar chart of the example absorber in the standard's Annex A: practical sound absorption coefficient in six octave bands, with the shifted reference curve and the weighted value of 0.60 with an M shape indicator, because the 500 hertz bar is far above the curve.0.00.20.40.60.81.0125250500100020004000500 Hz bar is 0.40 above the curve:shape indicator Moctave band centre frequency, HzWeighted value 0.60(M): the dashed curve is the reference curve shifted down 0.40Example values from the standard's Annex A (Figure A.2), redrawn
The Annex A example absorber with a 1.00 value at 500 Hz: practical coefficients as bars and the shifted reference curve as a dashed line. Values from ISO 11654:1997 Annex A, redrawn by Make Bespoke Studio.

What changes the number: face, backing and air space

Three things set how much a slatted wall absorbs, and a test report names all of them. These are general acoustic principles, not figures from the standard.

  • The face. The slats and the gaps between them let sound through to what is behind. A wider gap or a higher open fraction lets more through; a closed face reflects it. The slat width, gap and thickness are part of the product.
  • What sits behind. Sound that passes the face is only absorbed if there is something to absorb it: a felt, fibre or foam layer, or a porous backing. Without one, the slats behave much like a solid surface.
  • The air space. Depth between the absorbing layer and the hard wall behind it changes which frequencies are absorbed; more depth generally helps lower frequencies. ISO 11654 requires the depth of construction to be given for any product tested with an air space behind it, and notes that in Europe at least 200 mm is recommended (clause 5.4). The same panel fixed direct to a wall and fixed on battens is two different test specimens.

So a number from a test on a build-up with a deep cavity does not carry over to the same panel glued to plasterboard. The drawing shows two build-ups of the same layers with and without an air space. Our fluted, reeded and slatted profiles sheet covers slat and gap set-out, and our wall panelling styles sheet shows the slatted build-up.

Two build-ups: slats on felt on board, direct and on a cavityTwo sections through a wall. Left, slats over felt over a board fixed straight to the masonry. Right, the same slats, felt and board held off the masonry on battens, leaving an air space whose depth must be stated on the test report.air space DslatsfeltboardA. Direct: board, felt, slatsB. On battens: same layers plus air space
The same slats, felt and board fixed direct (A) and held off the wall on battens (B). Schematic, not to scale, and not a tested product. Original drawing by Make Bespoke Studio.

Reading a test report

When you are shown a figure for a slatted panel, check it against this table before you use it.

Check on the reportWhy it matters
Test standard and edition (BS EN ISO 354 and which edition) and rating standard (BS EN ISO 11654)The figures are only comparable if the method is the same. Both are listed by BSI as current, under review.
Laboratory and dateAn accredited laboratory (confirm with the accreditation body) and a date you can check against the product build.
Description of the specimen: slat width, gap, thickness, species, fixing, felt or backing, board, joint patternThe report covers that assembly only. Check each item against what is in your specification.
Mounting and depth of constructionISO 11654 clause 5.4 requires the depth of construction where there was an air space. Direct fix and battened are different results.
Test areaReported results are for a sample of defined area. Ask what area and how it was laid.
αp for each octave bandShows where the absorption is. Do not accept αw alone.
αw with any shape indicatorA letter in brackets means the product is much better in one range than the number suggests.
Fire classification of the same build-upA felt or foam layer needs its own classification evidence. See our fire performance of wall panelling sheet.

If the partner workshop has no report for the exact build-up, there are three honest answers: a report for a closely similar build-up with the differences stated (and the designer or acoustician accepting them), a new test for this assembly, or a design that the acoustician calculates from absorber data for the felt and the cavity. A bare absorption figure for a product in another build-up is not evidence for this one.

Other requirements and the limits of this sheet

The absorption figure is one requirement among several. A slatted panel on a wall also has to meet the fire requirements for a wall lining, and the felt and the glue have their own emissions; see our fire performance and formaldehyde and VOC emissions sheets. Approved Document E and BS 8233 are named in our research file as the references for sound in buildings; neither was read for this sheet, and reverberation targets for a project are set by the project acoustician, not read from this sheet. We give no typical absorption figures for any build-up: a figure is only worth having when it comes from a report for the assembly in your specification.

Specification wording

Paste into your schedule or specification and replace anything in [square brackets] with your own figures. Wording is a starting point: your specification governs.

Acoustic absorption of a slatted wall
Acoustic panelling ref [AP-01]: slats [18 x 45] mm at [24] mm gap on [6] mm felt on [12] mm board, [on 50 x 25 battens at 400 centres, forming a [50] mm air space / fixed direct], as detail [D-22]. The assembly is to have a reverberation-room test report to BS EN ISO 354 and a weighted coefficient to BS EN ISO 11654 of not less than αw [0.60], with practical coefficients for each octave band 250 to 4,000 Hz and any shape indicator stated. The report is for this build-up including the depth of construction, or is submitted with a written statement of every difference, accepted by [the acoustician] before ordering.
Evidence on submission
With the sample, the partner workshop submits the test report (laboratory, date, specimen description, mounting and depth, test area, αp table, αw with shape indicators) and the fire classification of the same build-up. Absorption figures for a different build-up are not accepted as a substitute.
No substitution
Slat width, gap, thickness, felt, board, fixing and cavity depth are as tested. A change to any of them is a variation requiring [the acoustician]'s written approval and, where the report no longer applies, a new test.

Terms used on this page

Reverberation
How long sound lingers in a room after the source stops; absorbing surfaces shorten it.
Sound absorption coefficient
The share of sound energy a surface absorbs rather than reflects, from 0 to 1, per frequency band, from a reverberation-room test.
αw (weighted sound absorption coefficient)
A single number between 0 and 1: the value at 500 Hz of a standard reference curve shifted down in 0.05 steps until the product's shortfalls below it total 0.10 or less. BS EN ISO 11654.
Shape indicator
A letter L, M or H after αw showing a band is 0.25 or more above the shifted curve at low, mid or high frequencies; read the full curve when one is present.
Depth of construction
The air space behind an absorber in the test; the standard requires it to be given with the result.

All joinery terms

Standards and sources

  • BS EN ISO 11654:1997 (ISO 11654:1997): BSI Knowledge: Current, Under Review; published 15 Nov 1997. Full text of clauses 1 to 5 and Annex A read in a publisher's preview on 7 Nov 2026; Annexes B and C were not in it.
  • BS EN ISO 354:2003: BSI Knowledge: Current, Under Review; published 9 Jun 2003. Listing only; the standard was not read.

Questions we are asked

What is a good αw for an acoustic panel?

There is no single answer and we give none. The target depends on the room, the other surfaces and the acoustician's brief. The standard also says the single number suits routine rooms such as offices, corridors and classrooms, and that a room needing careful acoustic design needs the full absorption data.

Is NRC the same as αw?

No. NRC is a United States single number and αw is the European rating from BS EN ISO 11654; they are calculated differently and the two should not be swapped in a specification. We have not read the US method, so we do not give its definition here.

What does the letter after αw mean?

A shape indicator. L, M or H after the number means the product absorbs at least 0.25 more than the shifted reference curve at low, mid or high frequencies, so the single number understates it in that range. Look at the full curve.

Why does the test report mention depth of construction?

Because the air space behind the panel changes the result, and ISO 11654 requires it to be stated whenever a product is tested with one. A panel tested on a deep cavity does not have the same rating fixed direct.

Can I take an absorption figure from a catalogue for my slatted panel?

Only if the catalogue's build-up matches yours: slat width, gap, felt, board, fixing and cavity. Otherwise get a report for your build-up or a written statement of the differences from your acoustician.

Does absorbing sound mean the wall blocks sound?

No. Absorption is about echo inside the room; insulation is about sound passing through a wall or door. See our acoustic doors sheet for insulation (Rw).

Download the factsheet

A two-page A4 PDF with the αw steps and the worked example, the six ratings compared, a test-report checklist and wording for an acoustic slatted wall.

Factsheet TL-JOI-45 v1.0 (PDF)