Compliance guidance. Figures are taken from the editions named, read in November 2026, and apply to England. This is guidance, not fire safety or legal advice. Which route applies to a headboard is open in the documents we read: the project fire strategy, a fire engineer, the fire risk assessor or your building control body decides, in writing. No product on this page is claimed to reach any class or pass any test.

At a glance

ElementRoute the sources we read point toEvidence to ask for
Fabric panel fixed to a wallWall lining: Approved Document B Volume 2 Table 6.1 (England), classes to BS EN 13501-1Test report or classification for the build-up, on the substrate it will be fixed to
Fabric wallcovering bonded to a wallTable 6.1 note 1: BS EN 15102 wallcovering of at least C-s3, d2 on an A2-s3, d2 substrate is acceptableEvidence that the product and the substrate match note 1
Headboard fixed to the wall (hotel)Open: either a lining (Table 6.1) or fitted furniture, which paragraph 6.3(d) leaves out of “wall”A written ruling from the fire engineer or building control, then a report as built
Headboard attached to the bed or standing free (hotel)No standard named in the sources we read. BS 7177 covers mattresses, mattress pads, divans and bed bases, not headboardsA written route from the fire risk assessor, then evidence for the headboard as built
Headboard in a private dwellingThe 1988 Regulations name beds and divans, including bases and headboards, for private use in a dwellingThe supplier's compliance statement against the Regulations
Hung fabric canopy or drapeBS 5867-2 covers non-domestic curtains, drapes and window blinds; whether it covers a canopy is to confirmThe assessor's written view, then a report for the fabric as hung
Panel with an acoustic or foam coreAny route: the test applies to the composite as built (Approved Document B paragraphs B2, B8)A report for the whole build-up, not one layer

England only; Wales, Scotland and Northern Ireland were not read. Approved Document B: 2019 edition with amendments to 2026, as published on GOV.UK in November 2026. Guidance, not fire safety or legal advice: no product is claimed to pass anything.

Start with what the element is

The question “which test?” has a different answer for each of four things that look alike. A fabric panel fixed to the wall is a lining of the room. A headboard is furniture when it belongs to the bed. A headboard fixed to the wall sits between the two. A hung canopy or drape is a furnishing. The drawing sets the routes the documents we read point to against each, and marks where none is named.

Two further points. Approved Document B’s Intention says it does not give guidance on furniture and fittings (Requirement B2), so furniture is dealt with elsewhere. And seating standards such as BS 5852, whose Crib 5 is often asked for, are written for upholstered seating, not headboards: BSI lists BS 5852:2006 as methods of test for the ignitability of upholstered seating. Do not accept “Crib 5” as an answer for a headboard without asking what it was tested as.

Upholstered headboards and wall panels: which route for which elementFour elements on the left and the route the sources point to on the right. A fabric wall panel fixed to the wall: wall lining classes in Approved Document B Table 6.1. A headboard in a private dwelling: the Furniture and Furnishings Fire Safety Regulations 1988 name headboards. A headboard in a hotel: no standard is named in the sources read, so ask the assessor and building control in writing. A hung fabric canopy: BS 5867 Part 2 covers curtains, drapes and blinds, and whether it covers a canopy is to be confirmed.Fabric wall panelfixed to the wallWall lining: Approved Document B Table 6.1(class in BS EN 13501-1 on its end-use substrate)Headboard in aprivate dwelling1988 Regulations name headboards(beds and divans, including bases and headboards)Headboard in a hotelor other non-domestic useNo standard named in the sources readAsk for the route in writing, then a report as builtHung fabric canopyor drape at the bedBS 5867-2 covers curtains, drapes, blindsWhether it covers a canopy: to confirmElementRoute the sources we read point toGreen: a route is named in a document read. Grey: no route is named, or the fit is unconfirmed.
Which route the documents we read point to for each element. Green: a route is named. Grey: none named, or the fit is unconfirmed. Original drawing by Make Bespoke Studio.

If it is a wall lining (England)

Approved Document B Volume 2 paragraph 6.1 says the surface linings of walls and ceilings should meet the classifications in Table 6.1. The table in the 2019 edition with amendments to 2026:

Where the lining is (England, Approved Document B Volume 2, Table 6.1)Class the surface lining should meet
Small room, up to 4 m2 floor area in residential accommodation (30 m2 in non-residential)D-s3, d2
Other roomsC-s3, d2
Other circulation spacesB-s3, d2 (note 1: a wallcovering to BS EN 15102 of at least C-s3, d2, bonded to an A2-s3, d2 substrate is also acceptable)

Three more points from the same document. Paragraph 6.4 allows parts of walls in rooms to be of lower performance than Table 6.1 but no worse than D-s3, d2, so long as the area of lower-performance lining in a room is less than half the room’s floor area, up to 20 m2 in residential accommodation and 60 m2 in non-residential; whether a panel may use that allowance is for the fire engineer. In the class, s1 to s3 grade smoke and d0 to d2 grade flaming droplets, and “s3, d2” means no limit is set on either (Appendix B paragraph B7). And a hotel is purpose group 2(b), “residential (other)” (Table 0.1); we read the table’s “residential accommodation” as including hotel bedrooms, which the fire engineer should confirm.

How the class is proved matters as much as the class. Appendix B paragraph B1 accepts a specification shown by specific test to meet the class, a design by relevant design standards, or an assessment of relevant test evidence in place of a test; paragraph B2 says small differences in fixing, joints, dimensions, insulation or an air gap might significantly affect performance; paragraph B8 says a classification is valid only when the product is fixed to a substrate of that class in its end use; and paragraph B5 says notified bodies or UKAS-accredited laboratories for the test standard can be assumed to have the expertise. Our fire performance of wall panelling sheet sets out Table 6.1 and the evidence for timber and board panelling in more detail.

If it is a headboard

The Furniture and Furnishings (Fire) (Safety) Regulations 1988, as revised, define furniture as furniture of any description ordinarily intended for private use in a dwelling, and include in it beds and divans, including the bases and headboards of both (regulation 3(1)). So a headboard in a private dwelling is named. The FIRA and British Furniture Confederation guide (2010, updated 2011), written for the contract and non-domestic sectors, says private dwellings are not covered by it and are covered by the Regulations, and that for most hotels and boarding houses the furniture risk level is considered medium, naming BS 7176 for seating, BS 7177 for mattresses, divans and bed bases, and BS 5867-2 Type B for curtains. It does not name a standard for headboards.

BSI describes BS 7177:2008+A1:2011 as the specification for resistance to ignition of mattresses, mattress pads, divans and bed bases. A headboard is not in that list. Whether a headboard fixed to the bed should be treated with the bed, as a piece of seating, as furniture under a risk assessment, or as a lining when it is fixed to the wall, is not answered in any document we read. So the page does not answer it either:

  1. Ask the fire risk assessor or the building control body which route applies to this headboard, and get the answer in writing.
  2. Ask whether the headboard is fixed to the wall (and, if so, whether it is a lining or fitted furniture under paragraph 6.3(d)) or to the bed.
  3. Ask the supplier for a test report on the headboard as built, to the route named, from a laboratory the assessor accepts.
  4. Record the route, the report reference and the date on your FF&E schedule: see our fire documentation matrix.

The wider domestic and contract picture is on our domestic or contract fire regulations sheet, and how to read a report is on how to read an upholstery fire test report.

Foam, acoustic cores and interliners: it is the whole build-up

A panel or headboard that is acoustic, foam-backed, interlined or all three is a composite. Approved Document B warns that small differences of fixing, joints, dimensions, insulation and air gaps can change performance and should be tested or assessed (paragraph B2), and that a classification holds only on the substrate class it was tested on (B8). Whatever the route, the report has to describe the panel you are buying: the board, the core, any interliner or treatment, the cover, how it is fixed, and what is behind it. A report for the cover fabric alone, or for the foam alone, does not cover a build-up it was not tested in.

A panel is classified as the composite that was testedA section through a fabric wall panel: wall, fixing, backing board, acoustic or foam core, interliner and cover fabric, from left to right. A bracket marks all the layers together as the composite that a fire test report applies to. Changing any layer, the fixing method or an air gap makes it a different composite.WallAir gap or fixingBacking boardCore: acoustic or foamInterlinerCover fabricthe composite the report applies toChange one layer, thefixing or the air gap andit is a different composite.Schematic, layers not to scale. The substrate behind the panel counts (Approved Document B B8).
A fabric panel in section. The report applies to the composite that was tested, on the substrate it will be fixed to. Original drawing by Make Bespoke Studio.

What to ask for

  • The route in writing. From the fire risk assessor or building control: lining, furniture, or something else, and the class or test it calls for.
  • The report or classification for the build-up. From a notified body or a UKAS-accredited laboratory for the test standard (paragraph B5), with the test standard and its edition named.
  • A description that matches the product. Layers, thicknesses, fixing method, air gap and the substrate behind; compare it line by line with the build sheet.
  • The date, and what changes it. A change to any layer, the fixing or the substrate means asking again.
  • The classes the building needs. Check the room: small room, other room or circulation space.

Specification wording

Paste into your schedule or specification and replace anything in [square brackets] with your own figures. Wording is a starting point: your specification governs.

Wall panel as a lining
Fabric wall panel to ref [P-01] to meet [class C-s3, d2] to BS EN 13501-1 as a wall lining to [room type] in [building], as set by [fire engineer] on [date]. Evidence: classification report for the panel as built (board [ ], core [ ], interliner [ ], cover [ ], fixing [ ], substrate [ ]) from a notified body or UKAS-accredited laboratory for the test standard, edition [ ].
Headboard, route to be confirmed
Headboard to ref [H-01], [attached to the bed / fixed to the wall]. Fire route confirmed in writing by [fire risk assessor / building control] on [date] as [ ]. The supplier is to provide a test report for the headboard as built (frame, filling, interliner, cover) to that route, laboratory, standard and edition stated, before production. A seating test alone is not accepted unless that route is named in writing.
Composite description
The test report is to describe the product supplied: layers and thicknesses [ ], fixing method [ ], air gap [ ], substrate [ ], and cover fabric reference [ ]. A report that does not match does not satisfy this clause.

Terms used on this page

Reaction to fire
How much a product contributes to a fire by its own decomposition, classified A1 to F to BS EN 13501-1 in Approved Document B Appendix B.
Wall lining
The surface of a wall or ceiling, which in England should meet the class in Approved Document B Table 6.1.
Composite
The combination of layers and fixings that was tested together; a report applies to that combination only.

All furniture terms

Standards and sources

Questions we are asked

What fire rating does an upholstered wall panel need in England?

A panel fixed to a wall is a wall lining, so its surface should meet the class in Approved Document B Volume 2 Table 6.1: C-s3, d2 in most rooms, D-s3, d2 in a small room (up to 4 m2 in residential accommodation), and B-s3, d2 in other circulation spaces. The class has to be proved for the panel as built, on the substrate it will be fixed to. A fire engineer or building control confirms the class for your room.

What fire test applies to a hotel headboard?

None of the documents we read names a standard for an upholstered headboard in a hotel. The 1988 Regulations name headboards for private dwellings only, and BS 7177 covers mattresses, mattress pads, divans and bed bases. Ask the fire risk assessor or building control for the route in writing, then ask the supplier for a report on the headboard as built.

Is Crib 5 the right test for a headboard?

Crib 5 is an ignition source in the seating test BS 5852. We found no source that makes it the route for a headboard. Ask what the headboard was tested as, and which route the assessor has named.

Does a foam or acoustic backing change the test?

Yes, because the report applies to the composite that was tested. Small differences of fixing, joints, insulation and air gaps can affect performance (Approved Document B paragraph B2), so ask for a report on the whole build-up, not the fabric or the foam alone.

Is a headboard fixed to the wall a wall lining or furniture?

The documents we read do not settle it. Approved Document B paragraph 6.3(d) leaves fitted furniture out of what counts as a wall, but whether a given headboard is fitted furniture is for the fire engineer or building control to say in writing.

Download the factsheet

A two-page A4 PDF: which route applies to each element, Table 6.1, what is open, what to ask for, and wording for a specification.

Factsheet TL-FUR-43 v1.0 (PDF)